Fault directory

Industrial drive fault-code records

Use a fault code as a controlled diagnostic entry point: define the indication, separate likely fault regions and choose the next test without unnecessary module replacement.

Blinking display
Danfoss VLT 2800 / VLT 2900: Blinking Display or Unstable Control Supply

The VLT 2800 display blinks, shows only partial segments, restarts during power-up or remains unstable even after keypad replacement.

Open →
Warning / Alarm 13
Danfoss VLT 2800 / VLT 2900: Overcurrent During Start, Ramp or Load

The compact VLT reports Alarm 13 or Warning 13 when the motor is started, during acceleration, under load or immediately at PWM output.

Open →
Alarm 14
Danfoss VLT 2800 / VLT 2900: Earth Fault on Motor Cable or Drive-Side Current Feedback

The drive trips with Alarm 14 during start, immediately after reset, with the motor connected, or even when the motor has been disconnected for testing.

Open →
Alarm 16
Danfoss VLT 2800 / VLT 2900: Current Short Circuit at Motor Terminals or Output Stage

The VLT 2800 / 2900 reports Alarm 16 on start, immediately after output enable, after motor work, after cable changes or after a prior power-stage repair.

Open →
F050
SIMOREG DC MASTER 6RA70: Optimization Run Not Possible or Interrupted

The SIMOREG 6RA70 reports F050 during a selected optimization run, often while commissioning, after a motor change, after parameter restoration or during speed-controller / current-controller tuning work.

Open →
F051
SIMOREG DC MASTER 6RA70: Optimization Run Setup or Parameter Memory Not Permitted

The drive refuses or cannot complete an optimization run because parameter write access, operating state, memory handling, commissioning sequence or setup conditions are not ready.

Open →
Speed feedback / tachometer instability
SIMOREG DC MASTER 6RA70: Speed Feedback or Tachometer Signal Instability

The 6RA70 becomes unstable, overspeeds, hunts, fails speed optimization, reports speed-feedback-related behavior, or runs differently after tachometer, encoder, motor or CUD1 work.

Open →
F005
SIMOREG DC MASTER 6RA70: Field Circuit Defective

The 6RA70 reports F005 during enable, run-up or field build-up, or the DC motor field chain cannot be confirmed even though the armature converter electronics appear alive.

Open →
F030
SIMOREG DC MASTER 6RA70: Commutation Failure or Armature Overcurrent

The 6RA70 reports F030 during current build-up, load application, reversing, acceleration, or after mechanical or armature-circuit disturbance.

Open →
No display / electronics supply
SIMOREG DC MASTER 6RA70: No Display or CUD1 Electronics Not Booting

The SIMOREG PMU or operator interface is dark, resets, shows unreliable status, or the converter cannot preserve a useful diagnostic state after power-up.

Open →
F521 / FieldAck
DCS800: Selected Motor Field Acknowledge Missing

The DCS800 reports F521, cannot confirm the selected motor field, or refuses to return to service because the field acknowledgement chain is not credible.

Open →
2340 / SHORT CIRC
ACS800: Output Short-Circuit, Phase-Leg or Power-Stage Fault

The ACS800 reports SHORT CIRC / 2340 at enable, first PWM, acceleration, steady operation or after a repaired module is returned to service.

Open →
5210 / PPCC LINK
ACS800: Control-to-Inverter Interface Communication Fault

The ACS800 displays PPCC LINK / 5210, sometimes with a module suffix or branch clue, and the drive cannot safely continue output operation.

Open →
E07
SJ300 / L300P Legacy Inverter Family: DC-bus overvoltage during deceleration, regeneration or high-line operation

The SJ300 / L300P trips E07 when the internal DC bus exceeds the overvoltage threshold. The trip may appear during deceleration, stop commands, descending or overhauling loads, high incoming AC voltage, or braking resistor / braking unit duty problems.

Open →
E01 / E02 / E03 / E04
SJ300 / L300P Legacy Inverter Family: Overcurrent by operating state, motor path or current-detection boundary

The SJ300 / L300P trips E01 at constant speed, E02 during deceleration, E03 during acceleration, or E04 under another operating condition such as DC braking, current-transformer error or noise-induced current detection.

Open →
E09
SJ300 / L300P Legacy Inverter Family: DC-bus undervoltage, input loss or control-power collapse

The SJ300 / L300P trips E09 at power-up, during a load step, after a line dip, during contactor operation, or together with keypad reset / blank display behaviour.

Open →
No display / dark keypad
SJ300 / L300P Legacy Inverter Family: Blank keypad, auxiliary supply failure or control-board load

The SJ300 / L300P has no keypad display, intermittent resets, no readable trip history, a dead front panel after a power event, or a used keypad / motherboard replacement that does not restore operation.

Open →
514C NO ARMATURE OUTPUT
Parker / Eurotherm 590P, 591P and 514C DC Drives: Analog command, field proof and SCR firing boundary before bridge repair

The 514C powers up and the machine has an enable or speed command, but the DC motor does not build usable armature voltage or torque. In other cases the output is intermittent, one direction is weak, or the motor only reacts when setpoint and enable wiring are disturbed.

Open →
514C FIELD LOSS / NO TORQUE
Parker / Eurotherm 590P, 591P and 514C DC Drives: Field supply absent, external field controller or unsafe no-torque condition

The 514C installation has no torque, weak torque, unstable speed, a field-loss suspicion, or a motor field that is supplied by a separate controller or transformer rather than the expected internal route.

Open →
514C BLOWN FUSE / BRIDGE FAULT
Parker / Eurotherm 590P, 591P and 514C DC Drives: Fuse clearing, SCR bridge short or armature circuit fault evidence

A 514C installation clears semiconductor fuses, trips the upstream protective device, shows a suspected bridge fault, or fails again after fuses are replaced.

Open →
590P SPEED FBK / ENCODER ALARM
Parker / Eurotherm 590P, 591P and 514C DC Drives: Speed-feedback mismatch, reversed feedback or missing tach / encoder evidence

A Parker / Eurotherm 590P or 591P reports a speed-feedback alarm, encoder failure, unstable speed regulation, overspeed tendency, speed collapse under load or a mismatch between armature-voltage feedback and a tachometer or encoder signal.

Open →
590P OVER I TRIP
Parker / Eurotherm 590P, 591P and 514C DC Drives: Armature overcurrent, unstable current loop or false current-feedback evidence

A Parker / Eurotherm 590P or 591P trips on OVER I TRIP during enable, autotune, current build-up, acceleration, reversing or apparently with little real armature load.

Open →
590P FIELD FAIL
Parker / Eurotherm 590P, 591P and 514C DC Drives: Field Supply Missing, Open Field or Field Feedback Fault

The 590P / 591P reports FIELD FAIL, cannot establish DC motor field current, or shows field feedback missing after the field should be energised.

Open →
590P MISSING PULSE
Parker / Eurotherm 590P, 591P and 514C DC Drives: Missing Thyristor Firing Pulse or Phase Reference Evidence

The DC drive reports MISSING PULSE, produces uneven armature current, or behaves as if one SCR firing channel or line-reference input is absent.

Open →
Alarm 7 / DC-link high
VLT FC Service Platform: DC Link Overvoltage During Deceleration

The VLT trips or warns on DC-link overvoltage when the machine slows, stops a high-inertia load, lowers a vertical load, or returns energy from the motor into the drive.

Open →
REPEAT-IGBT
FRENIC5000 G9 / G11 Repair Platform: Repeated IGBT / Power Module Failure After Replacement

Fuji FRENIC G9/G11 drive works briefly after a module replacement, then fails again, trips on output faults, produces unbalanced output, or damages another module under load.

Open →
RECTIFIER-SECTION
FRENIC5000 G9 / G11 Repair Platform: Integrated Module Rectifier Section Failure

Older Fuji or Japanese VFD module shows input/rectifier damage while the inverter section may still test differently, creating a repair-versus-replace decision for an expensive or scarce integrated module.

Open →
VCE-PROTECT
616G3: IGBT VCE Protection / Fast OC-GF Trip

Yaskawa 616G3-style driver stage removes gate pulses quickly during a module overcurrent, short-circuit, weak gate drive or abnormal collector-emitter voltage event.

Open →
F0001
MICROMASTER 430 / 440 Service Track: Overcurrent Fault

MICROMASTER 430 / 440 trips on F0001 during enable, acceleration, fast stop, pump start, fan inertia change or a blocked-load event.

Open →
F0002
MICROMASTER 430 / 440 Service Track: DC-Link Overvoltage Fault

MICROMASTER drive trips on F0002 during ramp-down, OFF3 fast stop, fan coast-down, pump check-valve slam, regenerative load or a high-line condition.

Open →
F0003
MICROMASTER 430 / 440 Service Track: Undervoltage Fault

MICROMASTER 430 / 440 trips on F0003 at power-up, after contactor pull-in, when other plant loads start, or during a weak-supply event.

Open →
F12
PowerFlex 520 / 750 Service Platform: HW Overcurrent Fault

PowerFlex drive reports F12 / HW Overcurrent, often at start, acceleration or during a sudden load event.

Open →
F13
PowerFlex 520 / 750 Service Platform: Ground Fault

PowerFlex reports F13 ground fault, sometimes intermittently and sometimes followed by a hardware-overcurrent trip.

Open →
F5
PowerFlex 520 / 750 Service Platform: DC Bus Overvoltage

PowerFlex reports F5 during deceleration, fast stop, lowering load or high line condition.

Open →
F4
PowerFlex 520 / 750 Service Platform: Undervoltage Fault

PowerFlex trips on F4 at power-up, when plant loads start, or after a supply dip.

Open →
F81-F86
PowerFlex 520 / 750 Service Platform: DPI Port Loss / HIM Communication Loss

PowerFlex 750-class drive trips on a DPI port-loss fault or loses communication with HIM, TCOMM, adapter or peripheral device.

Open →
OI.AC
Unidrive SP / Unidrive M Service Platform: AC Output Overcurrent Trip

Unidrive SP or Unidrive M trips on OI.AC during enable, acceleration, load change or unstable closed-loop operation.

Open →
Over Volts
Unidrive SP / Unidrive M Service Platform: DC Bus Overvoltage Trip

Unidrive trips on Over Volts during deceleration, hoist lowering, winder stop or high line condition.

Open →
PS.24V
Unidrive SP / Unidrive M Service Platform: 24 V Control Supply Overload / Fault

Unidrive reports PS.24V, loses option/module supply, or drops control logic when external loads are connected.

Open →
O.ht / O.ht1
Unidrive SP / Unidrive M Service Platform: Heatsink or Thermal Overload Trip

Unidrive reports O.ht or O.ht1 after load operation, high ambient temperature or poor cabinet cooling.

Open →
Feedback / encoder instability
Unidrive SP / Unidrive M Service Platform: Encoder Feedback Noise or Instability

Closed-loop Unidrive application is unstable, trips under load, hunts, overspeeds or reports feedback-related symptoms.

Open →
OCF
Altivar ATV61 / ATV71: Overcurrent Fault

The Altivar drive trips on OCF at run command, during acceleration or when the load changes.

Open →
SCF
Altivar ATV61 / ATV71: Motor or Output Short-Circuit Fault

The drive reports SCF or trips instantly when the output bridge is enabled.

Open →
OSF
Altivar ATV61 / ATV71: DC Bus Overvoltage / Supply Overvoltage

The Altivar drive reports OSF at power-up, while idle, during deceleration, on a regenerative load, or after braking hardware has been changed.

Open →
USF
Altivar ATV61 / ATV71: Undervoltage / Supply Loss Fault

The Altivar drive reports USF at power-up, drops ready state, trips after a run command, or shows undervoltage when the plant supply or line contactor changes state.

Open →
Alarm 14
VLT FC Service Platform: Earth Fault / Ground Fault

The Danfoss VLT reports alarm 14, trips on start or trips when the motor cable is connected.

Open →
Alarm 16
VLT FC Service Platform: Short Circuit

The VLT reports alarm 16 or trips instantly when the inverter output is enabled.

Open →
Alarm 4
VLT FC Service Platform: Mains Phase Loss

The VLT reports mains phase loss, trips at power-up, or loses ready state when plant load changes.

Open →
Alarm 29
VLT FC Service Platform: Heatsink Temperature Fault

The VLT trips on alarm 29 during load, in high ambient temperature, or after cooling airflow has degraded.

Open →
Overvoltage / DC link high
VLT FC Service Platform: DC Link Overvoltage During Deceleration

The VLT trips on overvoltage when the machine slows down, stops a high-inertia load or lowers a regenerative load.

Open →
3220 / DC UNDERVOLT
ACS510 / ACS550: Intermediate DC Circuit Undervoltage

The drive trips on DC UNDERVOLT / 3220, may not become ready, or may trip when load or line conditions pull the DC link below the permitted level.

Open →
ff51 / LINE CONV
ACS510 / ACS550: Line Converter Fault Indication

The drive reports LINE CONV / ff51 or points the technician toward the input/line-converter side rather than the motor output side.

Open →
2310 / OVERCURRENT
ACS510 / ACS550: Output Overcurrent During Start or Acceleration

The ACS510/ACS550 trips on OVERCURRENT / 2310 when a start command is issued, during acceleration, or under a sudden load condition.

Open →
FAULT LOG / RESET
ACS510 / ACS550: Fault History Review and Controlled Reset

The drive has a stored fault, intermittent trip history or a technician request to clear the fault without understanding the triggering condition.

Open →
KTY/PTC TEMP
SIMOVERT MASTERDRIVES 6SE70 / 6SE71: Motor Temperature Sensor Warning or Trip Boundary

The MASTERDRIVES system reports a motor-temperature warning/trip, or the temperature input behaves inconsistently after wiring, motor or board work.

Open →
BRAKE CONTROL
SIMOVERT MASTERDRIVES 6SE70 / 6SE71: Holding Brake Release / Close Timing Problem

A hoist, lift, crane or vertical axis does not release or hold correctly, or the drive/brake sequence causes movement, trip or mechanical shock.

Open →
NO DISPLAY
Cross-Brand VFD Fault Triage: VFD keypad dark or control power missing

The drive has line power present but the keypad stays dark, flashes briefly, clicks repeatedly or never reaches a ready state.

Open →
OC START
Cross-Brand VFD Fault Triage: VFD overcurrent trip at startup or enable command

The drive trips on overcurrent immediately at run command, during initial acceleration or before the motor reaches speed.

Open →
DC BUS OV
Cross-Brand VFD Fault Triage: DC bus overvoltage during deceleration

The drive runs normally but trips on overvoltage when stopping, ramping down, lowering a load or decelerating a high-inertia machine.

Open →
GF / EARTH FAULT
Cross-Brand VFD Fault Triage: Ground fault or earth leakage trip when the VFD runs

The drive powers up but trips on ground fault, earth fault or leakage indication during enable, acceleration or when output voltage is applied.

Open →
OUTPUT PHASE LOSS
Cross-Brand VFD Fault Triage: VFD output phase loss or motor phase missing indication

The drive reports output phase loss, motor phase loss, unbalanced output current or no torque on one phase.

Open →
REPEAT MODULE FAILURE
Cross-Brand VFD Fault Triage: IGBT or IPM module fails again after replacement

A replacement output module, IPM or IGBT pack fails during the first power-up, first run test or shortly after returning the drive to service.

Open →
590P OVER I TRIP
Parker / Eurotherm 590P, 591P and 514C DC Drives: False or real armature overcurrent

The digital DC drive trips before or during armature current command, and the technician must separate real load current from a corrupted current-feedback path.

Open →
590P FIELD FAIL
Parker / Eurotherm 590P, 591P and 514C DC Drives: Missing field current or open field circuit

The drive reports field failure, cannot establish motor field current, or detects zero field feedback after enable.

Open →
590P MISSING PULSE
Parker / Eurotherm 590P, 591P and 514C DC Drives: Thyristor firing or phase-pulse fault

The DC drive reports missing pulse or behaves as if one firing pulse, phase reference or thyristor bridge section is absent.

Open →
590P SPEED FBK / ENCODER ALARM
Parker / Eurotherm 590P, 591P and 514C DC Drives: Speed feedback mismatch

The drive cannot reconcile speed feedback with commanded operation or reports tachometer/encoder feedback alarms.

Open →
590P / 591P No Display
Parker / Eurotherm 590P, 591P and 514C DC Drives: No keypad or control power indication

The digital drive appears dead or loses interface power, requiring separation of incoming auxiliary supply, internal low-voltage rails and display/interface electronics.

Open →
514C No Armature Output
Parker / Eurotherm 590P, 591P and 514C DC Drives: Analog controller no-output condition

The 514C powers but provides no usable armature voltage or motor torque.

Open →
514C Field Loss / No Torque
Parker / Eurotherm 590P, 591P and 514C DC Drives: Field supply absent or motor field not established

The DC motor has no torque or unsafe behavior because field current is missing, weak or incorrectly wired.

Open →
514C Blown Fuse / Bridge Fault
Parker / Eurotherm 590P, 591P and 514C DC Drives: Input or armature bridge short suspicion

Fuses open or protective devices trip, requiring separation of external load short, bridge failure and wiring errors.

Open →
E01 / E02 / E03 / E04
SJ300 / L300P Legacy Inverter Family: Overcurrent by operating condition

Drive trips during constant speed, deceleration, acceleration or other running state.

Open →
E05
SJ300 / L300P Legacy Inverter Family: Electronic thermal overload

Drive trips after sustained load, incorrect motor data or cooling trouble.

Open →
E07
SJ300 / L300P Legacy Inverter Family: DC-bus overvoltage protection

Trip often during deceleration or regenerative load conditions.

Open →
E09
SJ300 / L300P Legacy Inverter Family: DC-bus undervoltage / input loss

Low-bus trip or unstable operation under input/load disturbance.

Open →
No display
SJ300 / L300P Legacy Inverter Family: No-display control-supply investigation

Blank keypad, intermittent reset or no fault code available.

Open →
Warning/Alarm 8
Danfoss VLT 2800 / VLT 2900: DC-link undervoltage / low intermediate circuit evidence

VLT 2800 reports DC LINK UNDERVOLT or trips before the motor can be run reliably.

Open →
Warning/Alarm 13
Danfoss VLT 2800 / VLT 2900: Overcurrent / peak current trip

The drive trips on overcurrent during start, acceleration or under load.

Open →
Alarm 14
Danfoss VLT 2800 / VLT 2900: Earth fault / output-to-ground leakage

The drive reports earth fault or trips when the output is energized.

Open →
Alarm 16
Danfoss VLT 2800 / VLT 2900: Current short-circuit / line-to-line output fault

The drive reports internal or output short-circuit and may trip immediately at run command.

Open →
Blinking / partial display
Danfoss VLT 2800 / VLT 2900: Control-board supply or display initialization problem

The VLT 2800 display blinks, only one digit illuminates or the LCP/panel replacement does not clear the symptom.

Open →
F1
VACON NXL: Overcurrent trip / output current surge

VACON NXL stops with F1 or a high-current trip during start, acceleration or under load.

Open →
F2
VACON NXL: DC-bus overvoltage / regenerative or supply event

The drive trips on overvoltage, often during deceleration or unstable supply conditions.

Open →
F3
VACON NXL: Earth fault / phase-current sum not zero

The drive trips with earth fault or output ground leakage during run command.

Open →
No display
VACON NXL: No display / dead control panel on inactive NXL drive

The NXL keypad or control panel does not initialize and the drive cannot be evaluated through normal fault history.

Open →
F005 / OverVoltage
PowerFlex 400: DC-bus overvoltage on PowerFlex 400

Drive trips with an overvoltage fault, often during deceleration, line events or attempts to start a suspect drive.

Open →
F004 / UnderVoltage
PowerFlex 400: DC-bus undervoltage or power-loss event

Drive faults during line sag, power cycling, startup, or large-frame operation where DC-bus ripple or input loss must be separated from internal power-stage evidence.

Open →
F081 / Comm Loss
PowerFlex 400: DSI / RS-485 communication loss

Drive reports F081, communication drops intermittently, the PLC/HMI loses control, or the drive reconnects automatically after network disruption.

Open →
Ground Fault / Output leakage
PowerFlex 400: Motor/cable leakage versus drive-side fault

Drive trips on ground fault or output-related protection during start/run, especially in fan and pump installations with long motor leads.

Open →
No display / no control power
PowerFlex 400: PowerFlex 400 no display or control-supply failure

The drive appears dead, display is absent, or control electronics do not initialize after line power is applied.

Open →
SCF1
Altivar 71 / ATV71: Motor short-circuit or output-ground fault route

ATV71 reports SCF1 or related SCF short-circuit fault during output enable, acceleration or operation.

Open →
SCF / IGBT short-circuit history
Altivar 71 / ATV71: SCF or IGBT short-circuit indication under generator or unusual source condition

ATV61/ATV71 displays motor short-circuit or IGBT short-circuit fault codes, sometimes in systems powered by a generator or non-ideal source.

Open →
USF
Altivar 71 / ATV71: Mains undervoltage / low DC-bus route

ATV71 shows USF or a low DC-bus condition, potentially during energization, acceleration, load operation or after a supply disturbance.

Open →
Blank / OFF display
Altivar 71 / ATV71: Blank display, off HMI or unable to read drive information

ATV61/ATV71 has a blank/off display, no keypad information, or a drive that cannot be interrogated normally from its HMI.

Open →
Power board repair / replacement decision
Altivar 71 / ATV71: ATV71 power-board repair, replacement or certified service route

A suspected failed ATV71 power board must be evaluated against spare-parts availability, Field Services restrictions, repairability and replacement-drive options.

Open →
No display / control supply missing
UE Frame 4 / Frame 5-7 Power-Board Families: PDL UE Frame auxiliary-supply or display-power failure route

The drive has no display, unstable control logic, or cannot initialize because the internal auxiliary supply is absent or unstable.

Open →
DC bus / precharge abnormal
UE Frame 4 / Frame 5-7 Power-Board Families: PDL UE Frame DC-bus and precharge evidence route

The drive trips on energization, shows bus-related instability, damages bus components, or cannot progress through a stable DC-link condition.

Open →
IGBT / gate-drive fault evidence
UE Frame 4 / Frame 5-7 Power-Board Families: PDL UE Frame IGBT gate-drive failure route

The drive trips around output enable, repeats power-module failure, or shows suspected phase-leg damage after an attempted IGBT replacement.

Open →
Comparator / protection trip
UE Frame 4 / Frame 5-7 Power-Board Families: PDL UE Frame LM339 protection-comparator route

The drive trips or blocks output with evidence pointing to protection logic, phase feedback or comparator-threshold behavior.

Open →
Repeated module failure after repair
UE Frame 4 / Frame 5-7 Power-Board Families: PDL UE Frame repeated IGBT or board failure after replacement

A replacement IGBT, power board or control board fails again after apparent repair, or the drive cannot be returned to reliable service.

Open →
POFF
EV1000 / EV2000 Control-Board Faults: EV2000 control-board POFF / power-off indication after board failure

Drive powers with POFF indication or board-level logic behavior suggesting supply or processor-side fault rather than a simple input-power absence.

Open →
E019
EV1000 / EV2000 Control-Board Faults: EV2000 current detection circuit fault

EV2000 displays E019 and may not reset or run, even when output current should be absent.

Open →
No display
EV1000 / EV2000 Control-Board Faults: EV2000 no-display logic-supply and board-short route

Keypad/display is blank or the board will not initialize, with possible 5 V / 3.3 V / reference rail involvement.

Open →
No display
EV1000 / EV2000 Control-Board Faults: EV1000 small control board 03025856 no-display route

EV1000 small-frame control board does not initialize the display or panel interface.

Open →
No output after repair
EV1000 / EV2000 Control-Board Faults: EV1000 no output after IGBT/IPM repair

Drive display recovers after a power-stage repair but run command produces no output, E019, or unsafe post-repair behavior.

Open →
HW Power Supply
Series 15H Inverter Control: Control power-supply malfunction indication

The Series 15H reports HW Power Supply, may fail to enable correctly, or may present unstable control behavior associated with its low-voltage electronics.

Open →
HW Ground Fault
Series 15H Inverter Control: Output leakage-to-ground fault investigation

The drive declares HW Ground Fault during run request or output energization, requiring separation of motor/cable insulation failure from internal drive-side protection activity.

Open →
BUS Overvoltage
Series 15H Inverter Control: High DC-bus voltage trip

The Series 15H trips with BUS Overvoltage, often requiring separation of line conditions, deceleration regeneration and dynamic-braking or internal measurement issues.

Open →
Bus Undervoltage
Series 15H Inverter Control: Low DC-bus voltage condition

The drive reports a low DC-bus condition or cannot maintain operation while the control electronics may still show status information.

Open →
NO DISPLAY / AUX
EDS1000: EDS1000-2S0015 No Display or Missing Control Power

The inverter is supplied correctly at its input but the display, control response, fan/relay readiness or low-voltage electronics are absent or unstable.

Open →
NO OUTPUT / DRIVE
EDS1000: EDS1000-2S0015 No Motor Output with Power Present

The control section appears alive and the unit may accept a command, but no usable U/V/W output is produced or an attempted start results in immediate protection.

Open →
FEEDBACK / CT
EDS1000: EDS1000-2S0015 Abnormal Current Feedback or Protection Behaviour

The inverter shows current-related abnormal behaviour, protection on attempted operation, or inconsistent evidence even after external motor/cable conditions have been investigated.

Open →
24 V OVP CASE
Starvert iS5: Control Supply Overvoltage on SV185iS5-4N0

A repaired LG / LS SV185iS5-4N0 shows abnormal or unstable low-voltage supplies; the nominal 24 V control rail may rise far above normal and endanger connected control electronics.

Open →
REPEAT DAMAGE
Starvert iS5: CPU Board Damaged Again After IGBT Repair

An iS5 drive initially presents with power-stage and CPU-board damage; after apparent repair and test power-up, the CPU board fails again.

Open →
UNSTABLE AUX
Starvert iS5: Unstable Auxiliary Power Before Control-Board Diagnosis

Low-voltage outputs fluctuate or rise together, creating misleading control-board, keypad or hardware-fault symptoms before the drive can be evaluated normally.

Open →
E.OC1
FR-A740: Overcurrent Trip During Acceleration

The FR-A740 trips as the motor begins to accelerate or immediately after a start command.

Open →
E.OV3
FR-A740: Regenerative Overvoltage During Deceleration or Stop

The FR-A740 trips while stopping a rotating load or reducing speed.

Open →
E.THT
FR-A740: Inverter Overload Trip

The drive stops after sustained high current without an instantaneous overcurrent trip.

Open →
SC
A1000: Output Short Circuit / IGBT Protection Trip

The A1000 trips immediately or under output demand with an SC indication.

Open →
GF
A1000: Ground Fault Diagnostic Route

The A1000 indicates GF during operation or immediately after a run command.

Open →
GF / Start-command trip
616G3: GF Indication and Protection-Path Misdiagnosis

A 616G3 drive powers normally but trips on the run command, or low-energy test indications suggest a short after IGBT replacement.

Open →
5210 / PPCC LINK
ACS800: Control-to-Inverter Interface Communication Fault

The ACS800 reports PPCC LINK, commonly as code 5210, and output operation is blocked or unreliable.

Open →
2340 / SHORT CIRC
ACS800: Inverter Output Short-Circuit or Power-Stage Fault

The ACS800 trips on SHORT CIRC during an enable/start attempt or immediately under load.

Open →
F521 / FieldAck
DCS800: Selected Motor Field Acknowledge Missing

The DCS800 reports F521 and cannot establish a valid field acknowledgement for the selected motor.

Open →
E019
TD900: Current Detection Circuit Fault

The drive reports E019 during power-up or operation, potentially without a genuine motor overcurrent event.

Open →
POFF
TD900: Input Undervoltage / Drive-Board Supply Indication

The keypad displays POFF immediately after power-up or only when the motor is commanded to run.

Open →
E010
EV1000: Module Protection Indication

EV1000 reports E010 either immediately at energization or when a run command is issued.

Open →
F002
SIMOVERT MASTERDRIVES 6SE70 / 6SE71: Pre-charging Fault

The drive does not complete DC-link precharge within the monitored period and prevents normal enable.

Open →
F006
SIMOVERT MASTERDRIVES 6SE70 / 6SE71: DC-Link Overvoltage

The MASTERDRIVES unit trips as the DC-link voltage rises above the permitted limit, often under regeneration or deceleration.

Open →
F008
SIMOVERT MASTERDRIVES 6SE70 / 6SE71: DC-Link Undervoltage

The drive disables pulses because DC-link voltage is below the permissible level for operation.

Open →
F011
SIMOVERT MASTERDRIVES 6SE70 / 6SE71: Overcurrent / Output-Stage Protection Path

The drive trips on excessive current; the OEM fault value can indicate the affected U, V or W phase in supported units.

Open →