Meaning of the indication
The route must separate motor lead, contactor, current sensor, gate-driver command and output power device evidence.
Checking order
- Confirm whether the symptom follows the motor/cable or stays with the drive output phase.
- Inspect output contactors, terminals and motor cable continuity under safe isolated conditions.
- Compare current feedback evidence with actual phase condition where qualified equipment is available.
- Check whether a previous IGBT repair left a driver, gate resistor or phase-current feedback fault unresolved.
Suspect areas
Output terminalMotor cableCurrent sensorGate driverIGBT phase leg
Diagnostic workflow
Workflow
VFD overcurrent-at-startup workflow
Open →WorkflowOvercurrent trip appears immediately at run command, during acceleration or before stable speed is reached.
VFD repeated IGBT/IPM failure workflow
Open →Replacement IGBT, IPM or output module fails again during power-up, enable or early load testing.