Danfoss fault record

Alarm 7 / DC-link high: DC Link Overvoltage During Deceleration

The VLT trips or warns on DC-link overvoltage when the machine slows, stops a high-inertia load, lowers a vertical load, or returns energy from the motor into the drive.

Deep technician fault route13 min read

Scope of this technical record

Danfoss VLT Alarm 7 / DC-link overvoltage route for deceleration, quick stop, high-inertia fan, pump coast-down, conveyor stop and lowering-load cases where regenerated energy may exceed the ramp or braking path.

Safety boundary

A drive in overvoltage or braking service can contain hazardous DC-link and brake-circuit energy after shutdown. Do not touch brake terminals or internal DC-link points until qualified isolation and discharge verification are complete.

Danfoss Alarm 7 brake-energy route

1Line voltage
2Stop event
3Ramp
4Brake path
5Bus feedback

The route separates line-side overvoltage from regenerated energy before chopper or board repair.

Danfoss VLT deceleration-overvoltage route

Danfoss VLT Alarm 7 route through line voltage stop event ramp brake chopper resistor and DC link feedback
The image keeps line-side voltage and regenerated load energy separate before brake-chopper or board conclusions.

Do not start by buying a brake resistor

A deceleration overvoltage trip is a symptom of energy management, not proof that one specific part has failed. The motor may be returning energy into the DC link because the ramp is too short for the load inertia, the application is overhauling, the line voltage is already high, or the brake path cannot absorb the energy.

The first decision is therefore simple but critical: is the voltage high before the stop event, or does it rise only when the machine decelerates? High line voltage and regenerated energy require different actions. A support request that skips this split tends to produce bad part advice.

Timing split for Alarm 7 / DC-link high

Trip timing is the fastest way to narrow the diagnostic scope. Alarm 7 at power-up points toward line or DC-link sensing evidence. Alarm 7 during deceleration points toward load energy, ramp or braking. Alarm 7 during lowering or unwinding points toward overhauling load behaviour, where the motor is acting as a generator for part of the cycle.

Deceleration overvoltage decision matrix

Observed patternMost likely boundaryEvidence that makes it actionable
Trip only when decel ramp is shortRegenerative energy / rampBefore/after ramp test and stop-time requirement
Trip on lowering or overhauling loadMachine energy entering DC linkLoad direction, torque direction and brake duty evidence
Trip with high incoming voltageLine-side voltageInput phase-to-phase readings at the drive
Resistor installed but hot or tripping thermalResistor duty or placementOhms, wattage/duty, thermal contact and cabinet heat
Resistor correct but no braking actionChopper command / brake transistorBrake option presence and chopper evidence
Overvoltage appears without regenerative eventDC-link sensing / control boundaryLine, ramp and brake evidence already ruled out

Brake path evidence before board repair

A board-level decision becomes credible only after line voltage, load inertia, ramp behaviour and the physical brake path have been documented. If a resistor is fitted, record its resistance after safe isolation, wiring route, thermal-contact state and cabinet placement. If no resistor is fitted, confirm whether the drive frame has a brake chopper or requires an external brake option.

The most common bad decision is replacing power electronics after every overvoltage trip. The better route is to prove whether the brake system was ever able to absorb the regenerated energy. Only then should the case move toward brake transistor, DC-link feedback or control-board investigation.

  • Record the exact stop event that creates Alarm 7
  • Capture input phase-to-phase voltage at the drive
  • Change ramp only as a controlled diagnostic when the process allows it
  • Verify brake resistor value and thermal circuit after isolation
  • Confirm brake-chopper option and command evidence before board repair

Field record checklist

  • Full type code and voltage class
  • Alarm/warning text and trip timing
  • Input voltage readings
  • Deceleration ramp setting and stop requirement
  • Load inertia or overhauling-load description
  • Brake resistor value, label, wiring and thermal-contact status
  • Previous resistor, chopper or drive-board replacement history

Technical basis and reference documents

This is an independent editorial technical reference. Original manufacturer documentation remains controlling for installation, repair and commissioning decisions.

Danfoss AC drives service tips — Alarm 7 DC-link overvoltageDanfoss

Defines Alarm 7 / DC-link overvoltage checks around input phase-to-phase voltage and regenerative voltage from the motor end.

Danfoss VLT AutomationDrive FC 301/302 Programming GuideDanfoss

Describes brake-resistor function as absorbing brake power generated in regenerative braking and supports the brake-energy route used here.

Danfoss article — Brake resistors, external is betterDanfoss

Explains why external brake-resistor placement can improve heat handling, duty-cycle selection and braking-energy dissipation.

Diagnostic workflow

Evidence intake

Turn this record into a qualified service request

A repair decision is much more reliable when the request includes the exact identity of the drive, the first fault evidence and the machine condition when the symptom appeared.

  • Complete drive type code / MLFB or nameplate model
  • Fault code, fault value and first event before reset
  • When the event appears: power-up, enable, ramp, run, decel or stop
  • Motor/cable connected or isolated during the symptom
  • Visible board, option-card, module and connector identifiers
  • Previous repair history, replacement parts and repeat-failure pattern
Prepare request →