Compact legacy AC drive / VFD family

Danfoss VLT 2800 / VLT 2900

VLT 2800 / 2900 service hub for compact-drive cases where a blinking display, DC-link undervoltage, Alarm 13 overcurrent, Alarm 14 earth fault or Alarm 16 short circuit must be separated into control supply, external motor/cable, current feedback, gate-driver and power-board evidence.

Series service hub11 min read

Scope of this technical record

Service hub for compact VLT 2800 / 2900 cases where display instability, overcurrent, earth fault, short circuit and board evidence must be separated before repair or replacement.

Safety boundary

Qualified drive personnel only. Isolate AC line supply and verify DC-link discharge before removing covers, motor leads, keypad assemblies or internal boards.

Danfoss compact-drive service route

1Display / fault
2Input / DC link
3Motor / cable
4Feedback / driver
5Repair / replace

VLT 2800 / 2900 cases are routed by symptom and evidence before keypad, board or replacement decisions.

Danfoss VLT 2800 / 2900 compact-drive route

Danfoss VLT 2800 2900 route through display input motor cable feedback driver repair decision
The visual route separates display, output-fault and board-evidence decisions.

Choose the route from what the drive actually shows

A compact VLT 2800 / 2900 case should not start with a board order. The first route depends on whether the drive can boot, whether the display is stable, and whether the first fault is Alarm 13, Alarm 14 or Alarm 16.

Blinking display cases stay on the control-power route. Alarm 13 is split by timing and load. Alarm 14 starts at the motor/cable insulation boundary and moves inward only when no-motor evidence points to the drive. Alarm 16 is treated as a short-circuit stop condition until the output path is proven.

First route selector

Observed caseStart withDo not jump directly to
Blinking / partial displayInput, DC link, auxiliary supply, +5 V / +24 V and keypad loadKeypad or control-board replacement
Warning / Alarm 13Trip timing, motor shaft, load, ramp and current-limit evidenceOutput module replacement
Alarm 14Motor cable, motor insulation, PE / shield and no-motor current evidenceCurrent sensor or power-board replacement
Alarm 16U/V/W terminal, cable, motor winding and output accessory short-circuit proofReset and re-run
Repeat failure after repairDC link, driver supply, gate channels, motor/cable proof and repair historyAnother module only

Compact drives need repair-versus-replace evidence

VLT 2800 and VLT 2900 drives are often old enough that service work includes a replacement decision. A useful service package records the type code, power size, board label, first fault, display behavior, motor/cable proof and previous repair history.

A donor drive or board is most useful when the original fault boundary is known. If a shorted motor cable, overloaded reference supply or unstable auxiliary supply is missed, replacement hardware can fail or repeat the same symptom.

Field record checklist

  • Type code
  • Power size
  • Display pattern
  • Fault number
  • Trip timing
  • Motor/cable insulation evidence
  • Input and DC-link evidence
  • Board labels
  • Previous repair history

Technical basis and reference documents

This is an independent editorial technical reference. Original manufacturer documentation remains controlling for installation, repair and commissioning decisions.

Danfoss service tips for VLT alarm boundariesDanfoss

Confirms Alarm 13 overcurrent, Alarm 14 earth fault, Alarm 16 current short circuit, input-phase and DC-link alarm boundaries used to structure the first service routes.

VLT 2800 Series instruction manualDanfoss

Documents VLT 2800 warning and alarm text including Alarm 13 peak current, Alarm 14 ground fault, Alarm 15 switch-mode supply and Alarm 16 short-circuit cautions.

Danfoss earth-fault service notesDanfoss

Provides practical Alarm 14 separation between motor/cabling evidence and drive-side current-sensor evidence, including no-motor current observations and manual-initialization caution.

Model records

Fault records

Blinking display
Blinking Display or Unstable Control Supply

The VLT 2800 display blinks, shows only partial segments, restarts during power-up or remains unstable even after keypad replacement.

Open →
Warning / Alarm 13
Overcurrent During Start, Ramp or Load

The compact VLT reports Alarm 13 or Warning 13 when the motor is started, during acceleration, under load or immediately at PWM output.

Open →
Alarm 14
Earth Fault on Motor Cable or Drive-Side Current Feedback

The drive trips with Alarm 14 during start, immediately after reset, with the motor connected, or even when the motor has been disconnected for testing.

Open →
Alarm 16
Current Short Circuit at Motor Terminals or Output Stage

The VLT 2800 / 2900 reports Alarm 16 on start, immediately after output enable, after motor work, after cable changes or after a prior power-stage repair.

Open →
Warning/Alarm 8
DC-link undervoltage / low intermediate circuit evidence

VLT 2800 reports DC LINK UNDERVOLT or trips before the motor can be run reliably.

Open →
Warning/Alarm 13
Overcurrent / peak current trip

The drive trips on overcurrent during start, acceleration or under load.

Open →
Alarm 14
Earth fault / output-to-ground leakage

The drive reports earth fault or trips when the output is energized.

Open →
Alarm 16
Current short-circuit / line-to-line output fault

The drive reports internal or output short-circuit and may trip immediately at run command.

Open →
Blinking / partial display
Control-board supply or display initialization problem

The VLT 2800 display blinks, only one digit illuminates or the LCP/panel replacement does not clear the symptom.

Open →

Board and assembly records

Circuit and diagnostic records

Circuit
Danfoss VLT 2800 +5 V / +24 V Control-Board and I/O Path

Low-voltage route for VLT 2800 blinking-display and control-board cases: DC-link feed, auxiliary supply start-up, +5 V logic, +24 V control, 10 V reference, keypad interface and external I/O load must be separated.

Open →
Circuit
Danfoss VLT 2900 Auxiliary Supply and DC-Link Path

Energy path for compact Danfoss cases where DC-link undervoltage, display instability or power-board suspicion must be separated from input fuses, rectifier, DC link and auxiliary supply behavior.

Open →
Circuit
Danfoss VLT 2900 Gate-Driver and Current Feedback Path

Output-stage route for Alarm 13, Alarm 14 and Alarm 16 cases after external motor, cable and terminal evidence has been collected. The route connects gate-drive channels, driver supply, current feedback and output module decisions.

Open →
Circuit
Danfoss VLT 2800 +5 V / +24 V Control-Board I/O Path

CB drawings expose +5 V, +24 V and VREF-related regions that help separate display initialization, keypad connection and control-card loading questions.

Open →
Circuit
Danfoss VLT 2900 Auxiliary Supply and DC-Link Reference Path

DB1 shows power-source and auxiliary rail evidence that supports undervoltage and post-repair rail-stability questions.

Open →
Circuit
Danfoss VLT 2900 Gate-Driver and Feedback Path

DB2-DB4 show isolated and buffered driver/feedback regions with rails and gate-signal families used when Alarm 13, 14 or 16 requires internal escalation.

Open →
Workflow
Danfoss VLT 2800 Blinking Display / Control Supply Workflow

Blinking, partial or unstable VLT 2800 display after power-up, keypad swap or repeated power cycling.

Open →
Workflow
Danfoss VLT 2800 Alarm 13 / Alarm 14 Output-Fault Isolation Workflow

Alarm 13 overcurrent or Alarm 14 earth fault on a VLT 2800 / 2900 compact drive during start, ramp, run or bench test.

Open →
Workflow
Danfoss VLT 2900 Alarm 16 / Gate-Driver Pre-Power Verification Workflow

Alarm 16 short circuit, repeat output-stage failure or post-repair uncertainty on compact Danfoss VLT 2900 hardware.

Open →
Workflow
Danfoss VLT 2800 Blinking Display / Control Supply Workflow

Blinking, partial or non-initializing VLT 2800 display after keypad replacement or power cycling.

Open →
Workflow
Danfoss VLT 2800 Overcurrent / Earth-Fault Isolation Workflow

Warning/Alarm 13 or Alarm 14 during run command, acceleration or output energization.

Open →
Workflow
Danfoss VLT 2900 Gate-Driver Pre-Power Verification Workflow

Alarm 16 current short-circuit, repeat module failure or post-IGBT repair risk.

Open →
Evidence intake

Turn this record into a qualified service request

A repair decision is much more reliable when the request includes the exact identity of the drive, the first fault evidence and the machine condition when the symptom appeared.

  • Complete drive type code / MLFB or nameplate model
  • Fault code, fault value and first event before reset
  • When the event appears: power-up, enable, ramp, run, decel or stop
  • Motor/cable connected or isolated during the symptom
  • Visible board, option-card, module and connector identifiers
  • Previous repair history, replacement parts and repeat-failure pattern
Prepare request →